MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

For Tanzanian site work, correct product selection should be followed by careful transport, connector inspection and retention of the fiber records. The 16FMMCMTPOM4 APC-to-UPC breakout divides sixteen OM4 fibers from one MMC APC female connector into two MTP-8 UPC female branches. It is built for multimode channels that require this precise polish combination. The direct fan-out replaces cassette-based conversion with one factory-tested unit and two visibly identifiable eight-fiber routes.

Product Highlights

  • MMC Female to MTP® Female, 16 Fibers
  • OM4 50/125μm, bend-insensitive fiber
  • MMC insertion loss ≤0.35dB, return loss ≥40/27dB (MMC/MTP®)
  • Harness Polarity wiring scheme
  • 2.5mm Plenum (OFNP) cable
  • Standard length options: 1m (3ft), 2m (7ft), 3m (10ft)

Specifications

Part Number16FMMCMTPOM4
ManufacturerHT
Connector AUS Conec MMC Female (Non-Pinned)
Connector BUS Conec MTP® Elite Female (Non-Pinned)
Polish TypeAPC to UPC
Glass FiberBend Insensitive Fiber
Fiber ModeOM4 50/125μm
Wavelength850/1300nm
Fiber Count16 Fibers
PolarityHarness Polarity
Cable Outside Diameter (OD)2.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)7.5mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)30N
Tensile Strength (Short Term)100N
Insertion Loss≤0.35dB
Return Loss≥40/27dB (MMC/MTP®)
Attenuation at 850nm≤2.3dB/km
Attenuation at 1300nm≤0.6dB/km
Operating Temperature-10 to 60°C (14 to 140℉)
Storage Temperature-10 to 70°C (14 to 158℉)

A mixed-polish multimode fan-out

APC at the MMC connector side and UPC at both MTP ends should be matched to the surrounding interfaces; the product configuration should not be substituted for the APC-to-APC breakout. The female, non-pinned connectors require pinned mates. Because the two MTP branches may serve distinct destination ports, label each of the branches and record its mapping before dressing the supplied cable into a manager.

Reflection and insertion-loss values by connector

Maximum insertion loss is 0.35dB. Return loss is specified independently as at least 40dB for the MMC APC interface and 27dB for the MTP UPC interface. Those figures must be retained in acceptance documentation rather than replaced by a single generic figure. Whereas reach remains determined by the specified transceivers, OM4 fiber supports the 850/1300nm multimode link.

Installing the two-leg assembly

The standard overall lengths are 1m (3ft), 2m (7ft) and 3m (10ft); custom meter and foot lengths are supplied. Location the branch point so neither MTP leg is pulled sideways, and respect the 7.5mm optical-fiber bend radius. Clean and examine the MMC and both MTP ferrules before making the three connections.

Ordering and Factory Support

Set out 16FMMCMTPOM4 in the APC-to-UPC two-branch model, with length and number of units. For repeat installations, custom branch IDs and a customer part-number label can keep these mixed-polish cables distinct from the APC-to-APC variants. For Tanzanian deliveries, the order details should include any site identification needed by the installation team.

You are here: Home 100BASE SFP MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

Tanzania Fiber Optics

China factory:ZYT Industrial Area,Shenzhen.
Tanzania Office:Ilala,Lumumba Str,
Dar es Salaam
Email:This email address is being protected from spambots. You need JavaScript enabled to view it.

Documentation

For products catalogue/data sheets or any general inquiry, please email info@huihongfiber.com and we will reply with details.

support